PRODUCT OVERVIE
SP-JXF low-voltage distribution box is applicable to three-phase three-wire, three-phase four-wire and three-phase five-wire systems of 400V and below or with load current not more than 630A for control, leakage protection, motor overload, short circuit and phase shortage. The box is designed according to the actual configuration, with reasonable design, small size, attractive appearance, novel structure, high protection grade, safe and reliable use. It can be widely used in power plant, rail transit, aerospace, petrochemical engineering, metallurgy, textile, real estate, steel and other industries for control and protection.
COMPLIANCE WITH STANDARDS
● GB/T72S1.12-2013 Low-voltage Switchgear and Controlgear Assemblies – Part 2: Power Switchgear and Controlgear Assemblies
● IEC61439-1 Low-voltage Switchgear and Controlgear Assemblies – Part 1: General Rules
● GB 10233 Basic Testing Method for Low-voltage Switchgear and Controlgear Assemblies
● GB17625.1-2003 Electromagnetic Compatibility- Limits -Limits for Harmonic Current Emissions (Equipment Input Current Per Phase ≤ 16A)
● GB 16838-2005 Environmental Test Methods and Severities for Fire Electronic Products
● GB 4208 Degrees of Protection Provided by Enclosure (IP Code)
● GB50171-2002 Code for Construction and Acceptance of Switchboard Outfit Complete Cubicle and Secondary Circuit Electric Equipment Installation Engineering
● GB14287.1~3-2005 Alarm and Control System for Electric Fire Prevention
3 TECHNICAL CHARACTERISTICS AND ADVANTAGES
Best surface protection
3.1.1 German environment-friendly and high-voltage electrostatic spraying automatic equipment is adopted
3.1.2 The vitrified membrane is formed on the surface of the spraying workpiece, and the surface coating of the product is uniform and attractive in color;
3.1.3 The membrane thickness after one-time spraying is 60μm〜80μm, and the precision error of coating thickness is ±20μm;
3.1.4 The spraying adhesion meets the national-level 0 standard, which can meet the 168h salt spray test;
Reliable electrical connection scheme
3.2.1 The miniature circuit breaker is connected by the customized busbar, to meet the requirements of temperature rise and electrical clearance;
3.2.2 The whole system is connected by national standard cable conductor, which is reliable;
3.2.3 The copper bar is processed by digital numerical control equipment with high processing accuracy, which effectively prevents the unreliable contact caused by the installation stress of the copper bar;
3.2.4 The advanced cold pressing terminal equipment ensures the reliable connection between the conductor and the components;
7+5 comprehensive test standards
Design verification according to IEC61439-1
| Structure inspection | Performance inspection |
| 1-Strength of materials and parts | 1-Dielectric property |
| 2-Protection class of complete equipment | 2-Verification of temperature rise |
| 3- Electrical clearance and creepage distance | 3-Short-circuit resistance strength |
| 4 – Integrity of protection against electric shock and protection circuit | 4-Electromagnetic compatibility |
| 5- Combination of switching devices and components | 5- Mechanical operation |
| 6 -Internal circuit and connection | |
| 7-External terminal |
4 Environmental Conditions for Use
4.1 The ambient air temperature shall not be higher than +40°C and not lower than – 25°C,and the average temperature within 24h shall not be higher than +35°C. Otherwise, the capacity shall be reduced according to the actual situation;
4.2 The altitude at the place of use shall not exceed 2,000m;
4.3 The relative ambient air humidity shall not exceed 50% when the maximum temperature is +40°C, and the high relative humidity is allowed at lower temperature (90% at +20°C).However, the change of temperature occasionally caused by the condensation shall be considered;
4.4 When the product is installed, the gradient with the vertical plane shall not exceed 5°;
4.5 The product shall be installed in a place without severe vibration and shock and that will not cause corrosion to the electrical components. The problem can be resolved through consultation with the manufacturer in case that users have special requirements.
5 Technical Parameters
| Technical parameters | SP-JXF |
| Rated current (A) | 630 |
| Rated insulation voltage Ui (V AC) | 690 |
| Rated operating voltage (V AC) | 400 |
| Rated impulse withstand voltage (KV) | 8 |
| Frequency (Hz) | 50 |
| Rated short-time withstand current Icw (KA/1S) | 20 |
| IP protection degree | ≤IP65 |
| Operation | Indoor, outdoor |
| Maximum altitude (m) | 2000 |
| Average ambient temperature (°C) | 35 |
| Pollution degree | 3 |
| Box material | Cold-roll steel sheet, stainless steel, ABS, and PC |
| Coating | Electrostatic spraying epoxy resin powder |
| Color | RAL7035 RAL7035 (industrial ash), customized |
| Insulation material inside the box | High temperature resistance and fire resistance |
7 Outline and Installation Dimension
SP-JXF outline and installing dimension


| Outline dimension | Height (H) | Width (W) | Depth (D) |
| 2520/14 | 250 | 200 | 140 |
| 3025/14 | 300 | 250 | 140 |
| 3025/18 | 300 | 250 | 180 |
| 3030/14 | 300 | 300 | 140 |
| 3030/18 | 300 | 300 | 180 |
| 4030/14 | 400 | 300 | 140 |
| 4030/20 | 400 | 300 | 200 |
| 5040/14 | 500 | 400 | 140 |
| 6040/20 | 600 | 400 | 200 |
| 6040/23 | 600 | 400 | 230 |
| 6050/14 | 600 | 500 | 140 |
| 6050/20 | 600 | 500 | 200 |
| 6050/23 | 600 | 500 | 230 |
| 7050/16 | 700 | 500 | 160 |
| 7050/20 | 700 | 500 | 200 |
| 7050/23 | 700 | 500 | 230 |
| 8060/20 | 800 | 600 | 200 |
| 8060/23 | 800 | 600 | 230 |
| 8060/25 | 800 | 600 | 250 |
| 10080/20 | 1000 | 800 | 200 |
| 10080/25 | 1000 | 800 | 250 |
| 10080/30 | 1000 | 800 | 300 |
7.1、SP-JXF outline and installing dimension

| Outline dimension | Height (H) | Width (W) | Depth (D) |
| 3025/15 | 300 | 250 | 150 |
| 3025/18 | 300 | 250 | 180 |
| 3030/15 | 300 | 300 | 150 |
| 3030/18 | 300 | 300 | 180 |
| 4030/15 | 400 | 300 | 150 |
| 4030/20 | 400 | 300 | 200 |
| 5040/15 | 500 | 400 | 150 |
| 5040/20 | 500 | 400 | 200 |
| 6040/15 | 600 | 400 | 150 |
| 6040/20 | 600 | 400 | 200 |
| 6050/15 | 600 | 500 | 150 |
| 6050/20 | 600 | 500 | 200 |
| 7050/15 | 700 | 500 | 150 |
| 7050/20 | 700 | 500 | 200 |
| 7060/15 | 700 | 600 | 150 |
| 7060/20 | 700 | 600 | 200 |
| 8060/20 | 800 | 600 | 200 |
| 8060/25 | 800 | 600 | 250 |
| 8070/20 | 800 | 700 | 200 |
| 8070/25 | 800 | 700 | 250 |
| 10080/20 | 1000 | 800 | 200 |
| 10080/25 | 1000 | 800 | 250 |
8 Ordering Instruction
When ordering, please note:
8.1 Model;
8.2 Installation method;
8.3 Structure form;
8.4 System diagram, and control schematic diagram;
8.5 The problem can be resolved through consultation in case of special requirements.