PRODUCT OVERVIEW
Electronic temperature sensors can control the on & off of heater according to the ambient temperature.
TECHNICAL DATA

| Switch temperature difference | 2K(±1K tolerance)at 25℃/77℉(50% RH) |
| Reaction time(humidity) | approx.5 sec. |
| Contact type | change-over contact(relay) |
| Contact resistance | <10mΩ |
| Service life | NC:>50,000 cycles NO:>100,000 cycles |
| Max.Switching capacity(Relay output) | NC:240VAC,6(1)A NO:240VAC,8(1.6)A NC:120VAC,6(1)A NO:120VAC,8(1.6)A 24VDC,4A |
| EMC | acc.to EN 55014-1-2,EN 61000-3-2,EN 61000-3-3 |
| Optical indicator | LED |
| Connection | 5-pole terminal,clamping torque 0.5Nm max.rigid wire 2.5mm² stranded wire (with wire end ferrule) 1.5mm² |
| Mounting | clip for 35mm DIN rail,EN6075 or for exit filter EF 118 Series |
| Casing | plastic according to UL94 V-0,light grey |
| Dimensions | 64.5x42x38mm |
| Weight | approx. 70g |
| Fitting position | variable |
| Operating/Storage temperature | 0 to+60℃(+32 to +140℉)/-20 to+80℃(-4 to +176℉) |
| Protection type | IP20 |
| Art.No. | Operating voltage | Setting range temperature | Setting range humidity |
| 01131.0-00 | 230VAC,50/60Hz | -20 to +60℃ | CSA-US(VDE submitted) |
| 01131.9-00 | 120VAC,50/60Hz | -4 to +140℉ | 140℉ CSA-US |